Products

pl series ın-line type frequency control circulation pumps

Materials:

  • Pump Body: Cast Iron GJL-250 (ASTM)(GG 25) - A48 Class 40-B (EN-DIN) - 0.6025 (DIN17007)  
  • Impeller: Cast Iron GJL-250 (ASTM)(GG 25) - A48 Class 40-B (EN-DIN) - 0.6025 (DIN17007)  
  • Seal: Mechanical  
  • Shaft: Stainless steel X20Cr13 (ASTM) - A 276 TYPE 420 (EN-DIN) 1.4021 (DIN17007)  

FRi Series Inline Ciculation Pump With Integrated Frequency Control Unit:
Frequency controlled glanded double pump in in-line design with flange connection and automatic power adjustment.
Energy savings due to integrated frequency control unit that receive the pressure information inlet and outlet transmitters.

Specifications Of Frequency Control Unit:
• 2• 16 characters LCD screen
• LINE / RUN/ GENERAL ALARM leds
• Mounting on motor with dedicated equipments
• Multipump (1 master + 3 slave) support
• IP 55 insulation class
• Easy Programming
• %120 overload up to 60 seconds
• Ambiance temperature 0 °C - 50 °C
• Adjusting output frequency (motor speed) using / buttons
• Adjustable output frequency by 2 digital input
• Programmable start-up and stoppage ramps
• Programmable pump sleep / wake up time for master pump
• Programmable pump start / stop time for slave pump(s)
• Automatic motor identification
• Data transfer to Building Automation System with RS485 interface via MODBUS
• Run with one 4-20 mA pressure transmitter on constant pressure mode, two 4-20 mA pressure transmitters circulation mode

Protections:
• Low Voltage Protection: Low Voltage Fault will be displayed when mains supply is lower  than %20 of nominal voltage
• High Voltage Protection: High Voltage Fault will be displayed when mains supply is higher than %20 of nominal voltage
• High Temperature Protection : Temperature Fault will be displayed when body temperature is higher than 80°C
• Phase Protection: Phase Fault will be displayed when one of the three phases of supply voltage is lost for three-phase drivers.
• Short Circuit Protection: Motor short circuit fault will be displayed when motor connection is short-circuited
• Minimum Pressure Protection: In case the system does not reach set pressure before set duration, pressure fault will be displayed  on screen but the system will not be blocked and the algorithm will try to reach set pressure for a few times more.
• Dry running protection with the help of floater